Greenhouse fan calculator.
Exhaust CFM, intake shutter area, and circulation airflow from your house dimensions. The same sizing our sales team quotes with.
| Fan | Rated CFM | Number needed |
|---|
One full air exchange every 1.5 minutes. Number needed is rounded up; growers usually split large CFM across two or more fans for staging.
| Shutter vent | Opening ft² | Number needed |
|---|
1.7 ft² of intake opening per 1,000 CFM of exhaust, on the wall opposite the fans.
| Circulator | Rated CFM | Number needed |
|---|
How the sizing works.
Summer exhaust is sized to change the full air volume of the house every 1.5 minutes: required CFM equals width times peak height times length, divided by 1.5. That target intentionally errs large, because a house that exchanges air fast enough on a July afternoon handles everything milder.
Exhaust fans only move what the intakes let in. Plan 1.7 square feet of shutter opening per 1,000 CFM on the wall opposite the fans, and the fans pull air the length of the house instead of fighting a vacuum.
Circulation is a different job: horizontal airflow (HAF) fans keep air moving when the house is closed up, evening out temperature and humidity. A commonly used rule from extension engineering references sizes HAF at about 25 percent of house volume per minute, laid out in a racetrack pattern, one row down each side.
About greenhouse ventilation.
Size exhaust to one full air exchange every 1.5 minutes: required CFM = width × peak height × length ÷ 1.5. A 30 × 96 gothic house works out to roughly 26,600 CFM, which growers usually split across two or more fans on one end wall. The calculator above runs the math for your dimensions.
Your house
Send us your sizing.
We'll confirm the airflow, match fans, shutters, and controls, and walk through placement. Your numbers come along with the form.